Hydronic Heating
-
-
-
-
WATTS Boiler Header Module Pro , Hydronic Package System (MPN: 235099)SKU: 1970424$773.15 23% off $1,005.10
-
Beacon-Morris, 55K84, Kickspace Heater, 115 V AC, 0.5 A, 60 hz, 1 to 3 gpm, 1/2 in (MPN: 55K84)SKU: 1872885$298.01 15% off $348.77
-
-
Beacon-Morris, K42, Kickspace Heater, 115 V AC, 0.5 A, 60 hz, 1 to 3 gpm, 1/2 in (MPN: K42)SKU: 1872883$381.47 20% off $476.84
-
-
Hydrolevel, 45-026, Water Feeder, 100 deg F, 150 psi, 1 gpm (MPN: 45-026)SKU: 19576$270.00 20% off $337.50
-
-
R.W. Beckett Beckett 51771U Igniter, For use with A, AF, AFG, NX, Thermoplastic (MPN: 51771U)SKU: 95105$62.26 29% off $87.18
-
R.W. Beckett Single-Stage CleanCut Oil Pump, 3 gph, 120V (MPN: PF20322U)SKU: 1993986$128.44 20% off $160.55
-
Tigerloop Ultra Oil De-aerator Oil De-Aerator, Spin-On Filter (MPN: S220-8)SKU: 1887687$182.83 23% off $237.67
-
-
-
-
-
-
Argo Baseboard 3" End Cap for Lo-Trim Baseboard, Right Hand (MPN: 55LT2-ECR-03)SKU: 1899096$12.62 27% off $17.36
-
Argo Baseboard 3" End Cap for Lo-Trim Baseboard, Left Hand (MPN: 55LT2-ECL-03)SKU: 1899095$12.62 27% off $17.18
-
R.W. Beckett PSC Burner Motor for use with Beckett AF/AFG/CF375 Burner (MPN: 21805U)SKU: 184015$89.38 21% off $113.78
-
McDonnell & Miller, 144692, Low Water Cut-Off, Automatic, 24 V (MPN: 144692)SKU: 148725$169.54 29% off $237.36
-
Hoffman 1/8" Adjustable Angle Steam Radiator Air Valve (MPN: 401422)SKU: 1920$61.06 29% off $85.50
Shop hydronic heating equipment and parts for closed loop hot water and steam systems, including boilers, circulator pumps, expansion tanks, aquastats, low water cutoffs, radiant heat controls, and oil burner parts, from brands including Taco, Honeywell, Zilmet, WATTS, Hydrolevel, McDonnell and Miller, Weil-McLain, and R.W. Beckett. Hydronic systems heat a building by circulating hot water rather than blowing heated air, which delivers steadier room temperatures with less noise and less dust movement than a forced air furnace, and works underfloor, through baseboard, or through cast iron radiators. Full buying guidance on how each component works, worked sizing examples, and selection mistakes to avoid is below the product listing.
Why Choose Hydronic Heat
Water carries far more heat per unit of volume than air, which is why a hydronic system can deliver the same heating capacity as a forced air furnace using smaller, quieter equipment and no ductwork blowing air or dust through the house. Hot water heat also holds its temperature more evenly, since a baseboard or radiant floor keeps releasing residual heat for a while after the boiler stops firing, rather than the on off temperature swing typical of forced air. Radiant floor systems in particular work under nearly any finished flooring, including tile, hardwood, and engineered wood, and are compatible with any fuel source that can heat water, including gas, oil, electric, and wood fired boilers. The tradeoff is that hydronic systems have more individual components working together than a simple furnace and duct system, which is exactly why matching the right part to the right job matters so much.
How a Hydronic System Works
A hydronic system heats water at a central source, moves that hot water through a closed loop of pipe using a pump, and releases the heat into a room through a radiator, baseboard, or radiant floor circuit before sending the cooled water back to be reheated. Every part on this page supports one of five jobs in that loop: generating heat, circulating water, controlling temperature and water level safely, managing pressure and trapped air in the closed loop, or delivering that heat into the living space. A separate steam category exists for true steam boilers, which move heat as vapor rather than circulated liquid water and use different safety controls than a hot water system.
Shop by Function
| Function | Categories on This Page | Role in the System |
|---|---|---|
| Heat Generation | Boilers | Burns gas or oil, or uses electric resistance, to heat the system water |
| Circulation | Circulators and Parts, Flow Control | Pumps heated water through the loop and regulates which zones receive flow |
| Temperature and Water Safety | Aquastats, Low Water Cutoffs | Controls water temperature and shuts the boiler down if water level drops too low |
| Pressure and Air Management | Expansion Tanks, Magnetic Separators | Absorbs water expansion as it heats and removes trapped air and ferrous sludge from the loop |
| Heat Delivery | Hydronic Baseboards, Kick Space Heaters, Radiant Heat Controls | Releases heat from the circulated water into the living space |
| Oil Burner Fuel System | Oil Products, Oil Nozzles | Delivers and atomizes fuel oil for combustion in oil fired boilers |
| Steam Systems | Steam Vents and Regulators | Releases trapped air from steam piping and regulates draft on steam boilers |
How These Parts Work Together as a System
These components are not independent purchases, they size off each other. A boiler's rated BTU output and its water content in gallons are the two starting numbers for everything downstream. The circulator has to be sized to move enough GPM for that BTU load, the expansion tank has to be sized against that same water content plus every zone and manifold added to the loop, and a magnetic separator or air eliminator has to be sized to the pipe diameter carrying that flow. Changing one component after the fact, such as adding a second radiant zone or swapping in a larger boiler, means revisiting the circulator and expansion tank sizing rather than assuming the original parts still fit the new load.
Heat Generation
Boilers
A hydronic boiler heats system water using a gas burner, an oil burner, or electric resistance elements, then sends that heated water out to circulators, zone piping, and heat emitters. Cast iron boilers are heavy, durable, and tolerant of lower return water temperatures, which historically made them the standard choice for older cast iron radiator systems. Modulating condensing boilers adjust their firing rate to match the actual heat demand rather than cycling fully on and off, extracting additional heat from flue gases in the process, which raises efficiency but requires the piping and controls to be designed for the lower return water temperatures condensing operation depends on. Two figures matter most when selecting a boiler: BTU input and output, which determine how much heating load it can cover, and the water content in gallons, which is required later to size the expansion tank correctly.
Circulation
Circulators and Parts
A circulator pump moves heated water through the piping loop using a spinning impeller, and correctly sizing one comes down to two numbers: flow rate in GPM and head loss in feet. Flow rate is calculated from the heating load using GPM equals BTU per hour divided by 500 times the design temperature drop, commonly 20°F. Head loss is the friction resistance of the water moving through the pipe, fittings, and components in that circuit, and it has to be checked against the specific pump's published performance curve at the required GPM, not just assumed. Undersizing a circulator for the head loss in its circuit means the pump cannot push enough flow to deliver the calculated GPM, while oversizing wastes electricity and can create excess noise and wear. This category includes cast iron circulators from Taco in cartridge and standard configurations for closed loop heating, along with bronze and stainless steel circulators used for open loop and domestic hot water recirculation applications where the water is not part of a sealed system.
Worked Example: Sizing a Circulator
| Step | Calculation | Result |
|---|---|---|
| 1. Find required flow rate | GPM = 60,000 BTU per hour divided by 500 times 20°F design drop | 6 GPM |
| 2. Estimate head loss | 150 feet of pipe times 1.5 fitting allowance times 0.04 feet of head per foot of pipe | 9 feet of head |
| 3. Match to a pump curve | Find 6 GPM and 9 feet of head on the manufacturer's published performance curve | Choose the smallest circulator whose curve sits above that point |
These numbers are for illustration. Always recalculate GPM and head loss from your own actual BTU load, pipe length, and pipe diameter, and always confirm the final selection against the specific pump model's published curve rather than these rounded example figures.
Temperature and Water Safety Controls
Aquastats
An aquastat is a thermostat for the boiler's water rather than the room's air, and it typically controls three functions. The high limit shuts off the burner once boiler water reaches its maximum set temperature, commonly around 180°F, protecting the boiler from overheating even if the room thermostat is still calling for heat. The low limit, used mainly on boilers that also produce domestic hot water through a tankless coil, keeps boiler water from dropping below a minimum temperature so hot water recovery stays fast. The differential is the gap between these set points that keeps the burner from short cycling on and off constantly. Most aquastats read boiler temperature through a sensor inserted into an immersion well, and that sensor needs heat transfer grease inside the well to read accurately. A dry well reads a falsely low temperature, which can let the burner keep firing well past a safe limit. This category includes Honeywell aquastat relays and combination controls used as direct replacements on most residential cast iron and oil fired boilers.
Low Water Cutoffs
A low water cutoff shuts the boiler's burner down if the water level in the system drops too low, which prevents the boiler from firing against dry or nearly dry heat exchanger surfaces, a condition that can crack cast iron sections or rupture steel ones. Low water cutoffs are standard equipment on virtually all steam boilers and are also installed on many hot water hydronic boilers as a safety backstop, even though water level is less visually obvious to a homeowner on a sealed hot water system than on an open steam system. Float type low water cutoffs use a mechanical float that drops with the water level and trips a switch, while electronic probe type units sense water level through a conductivity probe and are common on modern replacement installations. This category includes electronic automatic reset low water cutoffs from Taco and McDonnell and Miller.
Pressure and Air Management
Expansion Tanks
A closed hydronic system has nowhere for water to go as it heats and expands, so an expansion tank absorbs that extra volume using a compressible air or gas cushion held behind a diaphragm or bladder. The single most important rule in sizing and installing one correctly is that the tank's precharge pressure must equal the system's cold fill pressure. If precharge is set lower than fill pressure, system water partially compresses the air cushion before the system even starts heating up, which reduces the usable acceptance volume and is the leading cause of a waterlogged tank, chronic relief valve weeping, and ongoing water loss. This category includes diaphragm style expansion tanks from Zilmet sized for both residential heating loops and dedicated radiant zones.
Worked Example: Sizing an Expansion Tank
| Step | Input | Value |
|---|---|---|
| 1. Total system water volume | Boiler water content plus all zone piping and radiant loops | Example: 40 gallons |
| 2. Rough tank size estimate | Approximately 10 percent of total system volume as a starting estimate | Example: about 4 gallons of tank volume |
| 3. Set precharge pressure | Precharge must equal the system's actual cold fill pressure, commonly 12 psi on a typical residential system | Confirm with a tire gauge on the tank's Schrader valve before filling the system |
The 10 percent figure is a rough residential starting point, not a substitute for the full acceptance factor calculation, which also accounts for fill pressure, maximum operating pressure, and the temperature swing the system will see. Larger systems, systems using glycol, or systems with a high maximum operating pressure should have the tank sized from the full calculation rather than the rough estimate alone.
Magnetic Separators
Closed hydronic loops slowly generate magnetite, a black, abrasive iron oxide sludge produced by ongoing internal corrosion of steel and cast iron components in the system. Left circulating, magnetite accelerates wear on circulator pump seals and bearings and can foul the narrow internal passages of a modulating condensing boiler's heat exchanger, which is far more sensitive to sludge buildup than an older cast iron boiler's wider waterways. A magnetic dirt separator uses a magnet to continuously pull these ferrous particles out of the circulating water, protecting the pump and heat exchanger from the abrasive wear that untreated magnetite causes over years of operation.
Heat Delivery
Hydronic Baseboards
A hydronic baseboard heater runs hot water through a finned copper tube element mounted low on the wall inside a metal enclosure. As the fin tube heats the surrounding air, that air rises by natural convection and draws cooler room air in at the bottom of the enclosure, creating a continuous convective loop with no fan or blower required. This category includes cast iron baseboard sections as well as standard fin tube baseboard and the end caps and covers needed to finish an installation.
Kick Space Heaters
A kickspace heater places a small hot water coil and an electric blower inside the toe kick space beneath a cabinet, most often in a kitchen or bathroom where there is no wall space for a standard baseboard run. The blower forces air through the coil and out through a low grille, delivering the same hot water heat as a baseboard but through forced convection rather than natural convection, which lets it heat a space baseboard cannot reach. This category includes Beacon-Morris kickspace heaters sized by BTU output and gallons per minute of hot water flow.
Radiant Heat Controls
Radiant floor heating circulates hot water through PEX tubing embedded in or under a floor rather than through baseboard or radiators. A radiant manifold distributes water from the main supply line out to individual tubing loops, and flow meters at each manifold port let an installer balance flow between loops of different lengths. Zoning a radiant system is done either with thermostatically controlled actuators mounted directly on the manifold ports or with separate zone valves upstream of the manifold. Oxygen barrier PEX tubing is the correct choice for any radiant loop that shares system water with cast iron or steel components elsewhere in the system, since standard non barrier PEX is permeable enough to let dissolved oxygen diffuse into the water and accelerate corrosion of those ferrous parts.
Oil Burner Fuel System
Oil Products
An oil fired boiler uses an oil burner pump to draw fuel oil from the tank and pressurize it, typically to around 100 PSI, before sending it to the nozzle for atomization. An igniter, either an electrode spark assembly or a hot surface ignition element, provides the spark that lights the atomized oil spray. On systems where the oil tank sits below the burner or at a long horizontal distance, an oil de-aerator removes air that enters the fuel line, since air in the line causes an oil burner to lose prime and fail to start reliably. This category includes R.W. Beckett burner pumps, igniters, and burner motors, along with Tigerloop oil de-aerators.
Oil Nozzles
An oil nozzle atomizes pressurized fuel oil into a fine mist so it burns efficiently and completely rather than smoldering or sooting. Every nozzle is rated by three figures stamped on its body: a flow rate in gallons per hour, commonly in the 0.50 to 1.50 GPH range for residential equipment, a spray angle, typically between 60 and 90 degrees, and a spray pattern, either solid or hollow cone, which determines how the fuel mist is distributed inside the combustion chamber. Installing a nozzle with the wrong GPH rating changes the boiler's firing rate away from what its heat exchanger was designed for, which can cause incomplete combustion, soot buildup, or reduced efficiency even though the nozzle physically threads into place without issue.
Steam Systems
Steam Vents and Regulators
A steam heating system moves heat as vapor rather than as circulated liquid water, and it uses a different set of safety parts than a hot water hydronic system. Steam vents are installed on radiators and main piping to let trapped air escape as steam fills the system, since air left in the piping blocks steam from reaching the radiator and causes uneven heating. Draft regulators control the amount of air pulled through an oil or gas fired steam boiler's flue, stabilizing combustion efficiency against changes in chimney draft caused by wind and outdoor temperature. Because steam systems run at different pressures and use float type low water cutoffs almost universally, steam specific parts should not be substituted with hot water hydronic parts even when they appear similar.
Common Selection Mistakes
Most hydronic system failures trace back to one of a small number of mismatches. Setting an expansion tank's precharge pressure lower than the system's cold fill pressure waterlogs the tank before it ever does its job, leading to a relief valve that weeps on every heating cycle and a system that keeps losing water. Selecting a circulator based on GPM alone, without checking that flow rate against the pump's head loss curve for the actual circuit, results in a pump that cannot deliver the flow the load calculation called for. Skipping a magnetic separator on a system with a modulating condensing boiler lets magnetite sludge accumulate in a heat exchanger that has much less tolerance for debris than an older cast iron design. Installing an aquastat sensor into a dry immersion well without heat transfer grease causes it to read a falsely low temperature, which can let the burner run longer than intended. And using standard non barrier PEX on a radiant loop that shares water with cast iron or steel boiler components introduces dissolved oxygen that accelerates corrosion throughout the system. Adding a zone or upsizing a boiler without revisiting circulator and expansion tank sizing is another common oversight, since both were originally sized for the smaller load.
Frequently Asked Questions
Why choose hydronic heat over forced air?
Hydronic systems circulate hot water instead of blowing heated air, which delivers steadier room temperatures, runs quieter, and moves no dust or allergens through ductwork since there is no ductwork in a purely hydronic system. Radiant floor variants also work under nearly any finished flooring and can run off gas, oil, electric, or wood fired boilers.
What is the difference between an aquastat and a low water cutoff?
An aquastat controls water temperature, turning the burner off once the water reaches a set high limit and back on when it drops below a low limit. A low water cutoff is a separate safety device that shuts the burner down entirely if the water level in the system falls too low, regardless of temperature. Many boilers use both, since they protect against two different failure conditions.
How do I know what size circulator pump I need?
Start with the required flow rate using GPM equals BTU per hour divided by 500 times the design temperature drop, commonly 20°F. Then calculate the head loss of the specific circuit the pump will serve, based on pipe length, fittings, and any components like mixing valves or heat exchangers in that circuit. Only after you have both numbers can you check them against a specific pump's published performance curve to confirm it delivers that GPM at that head.
Why does my expansion tank keep waterlogging?
A waterlogged tank almost always means its precharge pressure is set lower than the system's actual cold fill pressure, so water enters and compresses the air cushion before the system even reaches operating temperature, leaving no room left to absorb thermal expansion. Check the tank's air charge with a tire gauge on its Schrader valve while the system is drained down, and reset it to match the system's fill pressure.
What is magnetite and why does it matter?
Magnetite is a black, abrasive iron oxide sludge produced by ongoing internal corrosion of steel and cast iron parts inside a closed hydronic loop. Left circulating, it wears down circulator pump seals and can foul the narrow internal passages of a modulating condensing boiler's heat exchanger, which is why a magnetic separator is commonly recommended on systems using this type of boiler.
Do I need oxygen barrier PEX for my radiant floor system?
Yes, if the radiant loop shares water with any cast iron or steel components elsewhere in the system, such as a cast iron boiler or steel baseboard elements. Standard non barrier PEX is permeable enough to let dissolved oxygen diffuse into the water, which accelerates corrosion of those ferrous parts over time. A radiant loop that is fully isolated from ferrous components through a heat exchanger can sometimes use non barrier PEX, but oxygen barrier tubing is the safer default.
Can I use a hot water low water cutoff on a steam boiler?
No. Steam boilers almost universally require float type low water cutoffs due to how water level behaves differently under steam pressure, and steam systems generally use different pressure ranges and safety controls than hot water hydronic systems. Always match the low water cutoff type to whether the system is steam or hot water rather than assuming one type works for both.
What causes an oil burner to smoke or run inefficiently?
The most common cause is a mismatched oil nozzle, either the wrong GPH flow rate for the boiler's designed firing rate or the wrong spray angle and pattern for the combustion chamber shape. Since these three specifications are stamped directly on the nozzle body, replacement nozzles should always match the original nozzle's exact GPH, angle, and pattern rating unless a technician has specifically recalculated the firing rate for the equipment.
If I add a heating zone, do I need to change any other equipment?
Usually yes. Adding a zone increases the total water volume and heating load on the system, which can push the existing circulator past its head loss capacity and undersize the existing expansion tank. Recalculate circulator GPM and head loss and recheck expansion tank sizing any time a zone, manifold, or major piping run is added rather than assuming the original components still fit.